CHAPTER 5: SETPOINTS
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
DETECT UNDERVOLTAGE
MESSAGE
BELOW 20V: NO
OVERVOLTAGE
MESSAGE
RELAY: OFF
OVERVOLTAGE
MESSAGE
LEVEL ≥
OVERVOLTAGE
MESSAGE
DELAY: 10.0 s
PHASES REQ'D FOR O/V
MESSAGE
OPERATION: ANY ONE
CURRENT UNBALANCE
MESSAGE
RELAY: OFF
CURRENT UNBALANCE
MESSAGE
LEVEL ≥
CURRENT UNBALANCE
MESSAGE
DELAY:
VOLTAGE UNBALANCE
MESSAGE
RELAY: OFF
VOLTAGE UNBALANCE
MESSAGE
LEVEL ≥
VOLTAGE UNBALANCE
MESSAGE
DELAY:
VOLTS PHASE REVERSAL
MESSAGE
RELAY: OFF
VOLTS PHASE REVERSAL
MESSAGE
DELAY:
DETECT I/V ALARMS USING PERCENTAGE: When "Yes" is selected, all current and
voltage alarms can be set in percentages of CT and VT. When "No" is selected, all
current and voltage alarms are actual voltage and current levels.
PHASE UNDERCURRENT RELAY: Undercurrent can be disabled, used as an alarm, or
as a process control feature. Set this setpoint to "Off" if the feature is not required.
Selecting "Alarm" activates the alarm relay and displays an alarm message whenever
an undercurrent condition exists. Selecting an auxiliary relay activates the selected
auxiliary relay for an undercurrent condition but no message will be displayed. This is
intended for process control.
PHASE UNDERCURRENT LEVEL: When the average three phase current drops to or
below the level set by this setpoint, a phase undercurrent condition will occur. Refer to
the
DETECT UNDERCURRENT WHEN 0A
undercurrent detection below 5% of CT.
PHASE UNDERCURRENT DELAY: If the average phase current is less than or equal to
the
PHASE UNDERCURRENT LEVEL
setpoint, a phase undercurrent condition will occur.
Range: No, Yes
Range: Alarm, Aux1, Aux2, Aux3, Off
Range: 20 to 65000 V in steps of 1, or
100 V
Range: 0.5 to 600.0 s in steps of 0.5
Range: Any One, Any Two, All Three.
Range: Alarm, Aux1, Aux2, Aux3, Off
Range: 1 to 100% in steps of 1
100%
Range: 0.5 to 600.0 s in steps of 0.5
10.0 s
Range: Alarm, Aux1, Aux2, Aux3, Off
Range: 1 to 100% in steps of 1
100%
Range: 0.5 to 600.0 s in steps of 0.5
10.0 s
Range: Alarm, Aux1, Aux2, Aux3, Off
Range: 0.5 to 600.0 s in steps of 0.5
1.0 s
setpoint description below to enable/disable
setpoint value for the time delay programmed in this
20 to 150% of VT in steps of 1,
set by the
DETECT I/V ALARMS
value.
USING PERCENTAGE
Not seen when
is set
VT WIRING
to "Single Phase Direct"
5–35