2.6

Optional Integrated Two-Button Assembly (Standard Display)

The Standard Display does not support all the transmitter configuration parameters and has limited
features.
The optional Integrated two-Button Assembly for the Standard Display provides the following
features and capabilities:
Menu and enter key functionality.
With the menu-driven display:
o Comprehensive on-screen menu for navigation.
o Transmitter configuration: enter LRV, enter URV and Loop Test.
o Transmitter calibration
o Display configuration (contrast only)
o Set zero and span parameters.
Revision 8.0
If you are using the optional external two-button assembly with the Standard
Display then you can perform all the above operations without removing external
glass cap using the external buttons
Lower range value (LRV): A display parameter (Standard display), which
allows users to enter the measuring value for which the analog output will
be scaled to 4mA.
Upper range value (URV): A display parameter (Standard display), which
allows users to enter the measuring value for which the analog output will
be scaled to 20mA.
ST 700 SmartLine Pressure Transmitters User's Manual