Figure 4-16 Cabinet And Floor-Planning Dimensions, Upflow, Cw106 And Cw114 With Forward-Curved Blowers - Emerson CW026 Design Manual

Liebert cw thermal management system
Hide thumbs Also See for CW026:
Table of Contents

Advertisement

Figure 4-16 Cabinet and Floor-planning dimensions, upflow,
CW106 and CW114 with forward-curved blowers
35"
889mm
CABINET
32"
813mm
PLENUM
FLANGE
76"
1930mm
120"
3048mm
BASE
SHADED AREA INDICATES
A RECOMMENDED CLEARANCE
OF 36" (914mm) BE PROVIDED
FOR COMPONENT ACCESS
AND FILTER REMOVAL. FOR
RECOMMENDED MINIMUM CLEARANCE
REFER TO THE INSTALLATION MANUAL.
BLOWER DECK
RIGHT SIDE OF UNIT
FRONT OR REAR
RETURN AIR
Chilled
Water
Model
Blower Supply
Top front
15 x 15
Top rear
CW106
CW114
Top front
15 x 11
Top rear 10 - 20
Cabinet and Floor-planning Dimensions—Upflow Models with Forward-curved Blowers
122"
3099mm
OVERALL
118"
2997mm
PLENUM FLANGE
SHADED AREA INDICATES
CLEARANCE OF 25" (635mm)
BE PROVIDED FOR REAR
RETURN FILTER REMOVAL
33"
838mm
BASE
AIR GRILLE MAY BE SUPPLIED
ON UNITS WITH FRONT RETURN
AIR ONLY.
F
Dimensional Data inches (mm)
Motor
HP
A
10 - 15 26-1/4 (667)
11-1/2 (292)
10 - 15
20
28-1/4 (718)
11-1/2 (292)
1" DUCT FLANGE FOR
PLENUM ALIGNMENT
FLANGES PROVIDED ON
BLOWER OUTLETS FOR
SUPPLY AIR DUCTING
A RECOMMENDED
ON ONE END OF UNIT.
4"
102mm
MODELS WITH REAR RETURN
122"
3098mm
C
C
E
FRONT OF UNIT
B
C
2-3/4 (70)
18-5/8 (473)
2-3/4 (70)
14-3/4 (375)
39
117 1/2"
FILTER ACCESS
2984mm
BOTH ENDS
AIR RETURN
OPENING
2 1/4"
57mm
22"
559mm
C
A
E
D
D
E
F
15-7/8
10
4-1/2
(403)
(254)
(114)
®
Liebert
CW
System Design Manual
24 1/4"
616mm
B
DPN003195
Rev. 2
Net Weight
lb (kg)
1785 (810)
1925 (873)

Hide quick links: