Requirements For Seismic Anchorage; Anchor And Load Requirements Of Seismic Installation; Table A-2 Downflow Liebert Cw Models On Floor Stand With 36" Plenum, Cw026-Cw081 - Emerson CW026 Design Manual

Liebert cw thermal management system
Hide thumbs Also See for CW026:
Table of Contents

Advertisement

Optional Configuration for Liebert CW Seismic Application
A.2 Requirements for Seismic Anchorage
A.2.1 Seismic Anchors
Mounting requirement details such as brand, type, embedment depth, edge spacing, anchor spacing,
concrete strength, wall bracing and special inspection must be outlined and approved by the project
structural engineer of record.
A.3 Anchor and Load Requirements of Seismic Installation
All floor and housekeeping pads must be approved by the structural engineer of record to resist the added
seismic loads from components being anchored as defined in this section. Data is presented by system
configuration. The maximum system loads are given for each loading location or floor stand foot. The
maximum load at the anchor is provided for proper sizing of the anchors (not provided by Emerson).
A.3.1 Seismic Anchorage Surface
Structural floors and housekeeping pads must also be seismically designed and approved by the project
structural engineer of record to withstand the seismic anchor loads as defined on the installation drawings.
The installing contractor is responsible for the proper installation of all anchors and mounting hardware,
observing the mounting requirement details outlined by the engineer of record. Contact the manufacturer's
representative if a detailed Seismic Installation Calculation Package is required.
NOTE
The floor stand used with EC units is not symmetrical, and its orientation to the Liebert CW is
critical to lowering the EC fans. Unless the floor stand is installed in the correct position, the
blowers will not lower into the floor stand.
NOTE
Load interactions must be considered when selecting anchors.

Table A-2 Downflow Liebert CW models on floor stand with 36" plenum, CW026-CW081

Model #
CW026-CW041DC1
CW051 CW060DC1
CW076-CW084DC1
CW089-CW114DC1
2
CW146-CW181DC1
1. Operating mass includes the operating water volume, floor stand and plenum.
2. 18" filter plenum only
®
Liebert
CW
System Design Manual
Floor
Stand
Operating
Restraint
Height
Mass 1
Locations
24
1108.1
48
1149.8
24
1538.4
48
1588.6
24
1881.1
48
1950.3
24
2589.5
48
2667.6
24
3136.5
48
3237
Maximum Load
per Anchor
Tension
Shear
4
554.8
155.1
4
778.6
160.5
44
648.2
211.8
4
913
218.4
6
533.1
175.6
6
753.5
181.7
6
722.7
241.7
6
1009.7
248.6
6
943
284.7
6
1233.8
294.5
82
Maximum Load per
Anchors
Location
per
Tension
Shear
Location
1164.6
310.5
1633.4
321.4
1426.8
423.5
2005.6
436.7
1169.5
351.4
1649.7
363.5
1611
483.4
2245.6
497.1
2017.7
569.6
2636.9
589.2
2
2
2
2
2
2
2
2
2
2