Figure A-2 Anchor Detail-Seismic Anchorage Rigid Floor Stand, Downflow, Cw026 - Cw181 - Emerson CW026 Design Manual

Liebert cw thermal management system
Hide thumbs Also See for CW026:
Table of Contents

Advertisement

Optional Configuration for Liebert CW Seismic Application
Figure A-2 Anchor detail—Seismic anchorage rigid floor stand, downflow, CW026 – CW181
ANCHOR DETA IL
TYPICAL 6 PLACES
2.5"
64mm
MIN. EDGE
DISTANCE
*MIN. PAD
THICKNESS
* SPECIFIED BY ENGINEER OF RECORD
FLOOR ANCHORING DIMENSIONS
A/2
2.0"
51mm
5.6"
143mm
Model Number
CW026, CW038, CW041
CW051, CW060
CW076, CW084
CW089, CW106, CW114
CW146, CW181
Anchor bolt sized per Hilti Kwik Bolt TZ carbon and stainless in concrete, ICC ESR-1917.
Alternates are subject to review by Emerson or engineer of record.
®
Liebert
CW
System Design Manual
ANSI B18.22.1
TYPE A, SERIES W PLAIN
WASHER REQUIRED AT
EACH ANCHOR LOCAITON
*MIN. EMBEDMENT
A
H
2.8"
70mm
TYP.
A
46.5 (1181)
70.5 (1791)
95.5 (2426)
118.5 (3010)
*MIN. HOLE
DEPTH
FIELD WELDING OF UNIT TO FLOORSTAND
1.0"
UNIT MUST BE WELDED TO FLOORSTAND TO MAINTAIN CERTIFICATION
25mm
TYP.
C
B
C
1/8" (3mm)
D
1.8"
TYP.
44mm
3.5"
TYP.
89mm
Dimensions in. (mm)
B
C
3.0 (76)
42.3 (1073)
4.0 (102)
54.3 (1378)
6.0 (152)
86
Anchor
D
Size
4.0 (102)
1/2
6.0 (152)
8.0 (203)
C
C
D
DPN003209
Pg. 3 Rev. 2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents