Figure A-10 Seismic Piping Considerations - Emerson CW026 Design Manual

Liebert cw thermal management system
Hide thumbs Also See for CW026:
Table of Contents

Advertisement

Optional Configuration for Liebert CW Seismic Application

Figure A-10 Seismic piping considerations

Unit
Anchor piping
to unit
Prefabricated seismic
compensation piping
FLOOR MOUNT
Flexible Loops:
All units, either rigidly mounted or mounted on vibration isolators, shall be attached to the piping system using flexible loops designed for seismic
movement. Flexible loops shall be capable of movement in the ±X, ±Y, and ±Z planes and must completely isolate the equipment from the piping.
The loops shall be suitable for an operating pressure and temperature of the system, refer to Liebert installation instructions. This includes 1/4"
copper humidifier supply, condensate drainage, and chilled water supply and return. Follow manufacturer's installation instructions for proper
seismic application of flexible loops.
®
Liebert
CW
System Design Manual
Anchor to
foundation
Seismic compensation device
FLEXIBLE LOOP EXAMPLE
94
Unit
Secure pipes to floorstand
Prefabricated seismic
compensation piping
Anchor Piping
FLOORSTAND MOUNT
Upflow with floorstand: anchor to floorstand
Upflow rigid mount: anchor to unit
Downflow: anchor to floorstand
To unit
DPN003209
Pg. 9 Rev. 2