Troubleshooting by Indication on the Remote Controller
3.20 "E7" Malfunction of Outdoor Unit Fan Motor
E7
Remote Control
Display
Applicable Models
ER*Q 011~016*
Method of
Malfunction of fan motor system is detected according to the fan speed detected by hall IC when the fan
Malfunction
motor runs.
Detection
When the fan runs with speed less than a specified one for 6 seconds or more when the fan motor
Malfunction
Decision Conditions
When malfunction is generated 4 times, the system shuts down.
Malfunction of fan motor
Supposed Causes
The harness connector between fan motor and PC board is left in disconnected, or faulty connector
Fan does not run due to foreign matters tangled
Clearing condition: Operate for 5 minutes (normal)
Open phase L1 or open phase N.
168
running conditions are met
ESIE09-08A