Field Setting
[2] Automatic setback function
First
2
Setback function provides the possibility to lower the room temperature. The setback function can for
instance be activated during the night because the temperature demands during night and day are not the
same.
Notes :
1. By default the setback function is enabled, if it's not needed, it should be disabled.
2. The setback function can be combined with the automatic weather dependent set point operation.
3. Setback function is an automatic daily scheduled function.
4. It is advised to set the start time of automatic storage during night [1-01] on the moment that the
 [2-00] Status: defines whether the setback function is turned ON (1) or OFF (0)
 [2-01] Start time: time at which setback is started
 [2-02] Stop time: time at which setback is stopped
* Setback operation for room temperature control
[5-03] 18°C
* Setback operation for leaving water control
A
B
Notes :
1. In setback operation for room temperature control, immediately a setback temperature is set.
2. In setback operation for leaving water control, a shift down value is chosen. This value should be
98
Second
code
code
Setting name
Automatic setback function
00
Status: setback operation
01
Setback operation start time
02
Setback operation stop time
setback function starts [2-01].
T
A
21°C
[2-01]
A
Normal room temperature set point
t
Time
T
Temperature
[5-03]
Room setback temperature (actual temperature)
T
65°C
5°C [5-02]
60°C
[2-01]
A
Normal leaving water temperature set point
B
Leaving water setback temperature
t
Time
T
Temperature
[5-02]
Leaving water setback value (shift value)
lowered from the normal set point.
t
[2-02]
t
[2-02]
Default
value
Range
Step
1 (ON)
0/1
23:00
0:00~23:00
1:00
5:00
0:00~23:00
1:00
Test Operation
ESIE09-08A
Unit
hour
hour