ESIE09-08A
3.38 "L1" Indoor Unit: Malfunction of PC Board
L1
Remote Control
Display
Subcode 30
Applicable Models
All indoor units
Detect malfunctions by current value during waveform output before compressor startup.
Method of
Detect malfunctions by current sensor value during synchronized operation at the time of startup.
Malfunction
Detection
In case of overcurrent (OCP) during waveform output
Malfunction
When the current sensor malfunctions during synchronized operation
Decision Conditions
In case of IGBT malfunction
Faulty indoor PC board [A4P (1
Supposed Causes
Troubleshooting
Troubleshooting
Over current
Current sensor failure
Failure of IGBT or drive circuit
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Turn OFF the power
supply once and then turn
it ON again.
YES
Does it return
normally?
NO
Troubleshooting by Indication on the Remote Controller
ø
ø
) or A5P (3
)]
It is believed that external
factors (noise, etc.) other
than failure caused the
malfunction.
Replace the indoor PC board
ø
ø
[A4P (1
) or A5P (3
)].
(PC board equipped with a
resin case)
189