The maximum length cable length between the Control Panel and
the First Remote Unit, or between each Remote Unit must not
exceed the following distances unless a Repeater Unit is used.
MICC (lightweight) 4-core
MICC (heavyweight) 4-core Distance between units not to exceed 200m.
FP200 4-core
FP Plus 4-core
The following table states nominal resistance values for the
different types of cable normally encountered.
Table A.1 — Resistance Values for Different Cable Types
Cable Type
FP200 1.0mm
FP200 1.5mm
FP200 2.5mm
MICC 1.0mm
MICC 1.5mm
MICC 2.5mm
L
ABLE
ENGTHS AND
Distance between units not to exceed 150m.
Distance between units not to exceed 200m.
Distance between units not to exceed 200m.
DCΩ per KM
Max DCΩ per single link
18.1Ω
12.1Ω
7.4Ω
17.2Ω
11.4Ω
6.8Ω
Installation & Commissioning Manual
3.62Ω
2.42Ω
1.48Ω
(LW) 2.58Ω
(HW) 3.44Ω
(LW) 1.71Ω
(HW) 2.28Ω
(LW) 1.02Ω
(HW) 1.36Ω