4.4.3 Connecting Batteries

54
Connecting the batteries to the Control Panel should only be
performed after the wiring checks in Section 4.4.1 and Section
4.4.2 have been completed successfully.
N
: If this procedure is not followed the Control Panel may display a
OTE
"Charger Fault".
1. Disconnect the Mains Power from the Control Panel.
Wait for 10 seconds.
2. Connect the Batteries to the Control Panel.
N
: THE BATTERIES MUST BE CONNECTED BEFORE
OTE
THE MAINS POWER.
3. Re-connect the Mains Power to the Control Panel,
4. Press the "RESET" button to remove the "PROCESSOR
RESTART" fault LED.
5. The Green "System OK" LED should now illuminate.
N
: The Control Panel will not operate on Batteries until the Mains
OTE
Power has been applied.