Fire Telephone Remote Units (Bvfhl) - Baldwin Boxall OmniCare Installation Manual

Evc system
Table of Contents

Advertisement

C O M M U N I C A T I O N S

4.5.4 Fire Telephone Remote Units (BVFHL)

OmniCare issue 1
1. Open the door and check the "SYSTEM OK" LED is flashing.
2. Lift the Handset at the Remote Unit.
Both the Remote Unit and the Control Panel will 'ring'. The
associated red LED on the Control Panel(s) will flash to
indicate activity at that Remote Unit location.
3. Check that when the Handset at the Control Panel is lifted
and the zone is selected communication can be established.
N
: If only one Remote Unit is calling the Control Panel then that call
OTE
is automatically answered by lifting the handset.
4. Set the Volume on the
The volume control (as shown in Figure 3.8 on page 30) sets
the level of Control Panel speech (and the level of the ring
tone) reproduced at the
to allow speech to be clearly understood.
5. Replace the Handset on the Remote Unit.
Ensure the relevant red LED on the Control Panel
extinguishes.
6. Lift the handset on the Control Panel and press the relevant
Zone Button.
Ensure the Remote Unit starts to ring.
N
: If a Beacon is fitted to the Remote Unit then it should flash while
OTE
the unit is being called from the Control Panel.
7. Press the PTT button on the Control Panel. Ensure the
operator can be heard from the loudspeaker in the Remote
Unit.
8. Release the PTT on the Control Panel. Ensure the operator
can hear the microphone on the Remote Unit.
9. Replace the Handset at the Control Panel and ensure the
relevant Red LED extinguishes.
.
Remote Unit
and should be adjusted
Remote Unit
OmniCare EVC System
Installation & Commissioning Manual
57