Technical Specifications; Control Panels - Baldwin Boxall OmniCare Installation Manual

Evc system
Table of Contents

Advertisement

OmniCare EVC System
Installation & Commissioning Manual
1.2 T
ECHNICAL

1.2.1 Control Panels

Control Panels
System self-monitoring
Remote signalling of fault
Indicators
Transmission capability
Power supply
Power consumption (VA)
Dimensions (W x H x D)
Bezel dimensions (W x H x D) 461mm x 340mm x 25mm (8-32 way)
Bezel Cutout dimensions W x H 420mm x 300mm (8-32 way)
Knockouts
Security
Weight, including batteries
Temperature Range
Humidity Range
2
S
PECIFICATIONS
BS5588 & BS5839 compliant
Volt-free contact, closing/opening set on installation
Occupied, call, fault, power, charger, speech level
Half-duplex (DRS remotes) either voice switched or by
PTT (controlled at the Control Panel).
Full Duplex (Fire Telephones)
110V / 230V AC autoswitching, battery backed with built
in batteries & charger
10VA + 1VA per remote connected
410mm x 290mm x 200mm (8-32 way)
410mm x 455mm x 200mm (16-64 way)
410mm x 777mm x 200mm (80-128 way)
Bezel dimensions: 461mm x 506mm x 25mm.
Bezel cut out dimensions: 420mm x 465mm.
461mm x 506mm x 25mm (16-64 way)
420mm x 465mm (16-64 way)
20mm diameter in top and top/rear
Lockable glazed door
21kg upto 32way, 26kg upto 64way, 37kg upto 128way
-10 to +30°C (storage and operating)
95% Non Condensing
Figure 1.1 — Typical OmniCare Control Panel