OmniCare EVC System
Installation & Commissioning Manual

3.2.5 Disabled Toilet Alarm (BVOCDTA)

3.2.5.1 Connection to Circuit Cabling
36
The Disabled Toilet Alarm uses a BVFREPEM Repeater to
interface with the OmniCare EVC System.
Refer to Figure 3.1 on page 20 for details of the mounting holes
for the back box of the BVFREPEM.
Comprehensive wiring instructions are included within the
Disabled Toilet Alarm kit.
1. If possible, before connecting the Remote Units check the
Circuit Cabling for Short Circuits, Open Circuits, shorts to
Ground, and Correct Phasing of all conductors.
2. If not already fitted, mount the supplied back box at each
Remote Unit location.
3. At the rear of the
Figure 3.13) to release the brackets retaining the blue
termination blocks.
Figure 3.13 — Rear View of BVFREPEM Remote Unit
A
Circuit Cable Termination Block under removable bracket
B
Removable Bracket securing screws
C
Option Connector Block under removable bracket
D
LK1, LK2 & LK3 - refer to Section 3.2.5.2 for details
E
MODE switch - refer to Section 3.2.5.2 for details
remove the screws (item B in
Remote Unit
C O M M U N I C A T I O N S
OmniCare issue 1