1.3.2 System Status & Fault LEDs
Colour
1
Green
2
Yellow
3
Yellow
4
Yellow
5
Yellow
6
Yellow
7
Yellow
8
Yellow
9
N/A
10
Yellow
11
Green
12
N/A
OmniCare issue 1
Figure 1.9 — System Status & Fault LEDs
Ident
Description
Mains On
Mains supply Connected and Healthy
Battery High
Battery Voltage too High (Overcharged) *
Battery Low
Battery Voltage too Low (Faulty battery) *
Charger Fault
Will illuminate if the batteries are unable to hold their
charge or if they are not fully charged after 24 Hours
charging.
Reset (9) must be pressed to clear a charger fault.
Fuse Fault
Will illuminate if any internal DC fuse fails.
Common Fault
Will flash and a buzzer will sound when a Fault is
detected until "Fault Accept" (12) is pressed.
After a fault is accepted the buzzer is silenced and the
LEDs remain illuminated until the fault is cleared.
Processor Fault
Will illuminate if a critical Processor fault has occurred.
Processor Restart
Will illuminate if the Reset Switch (9) needs to be
pressed.
Reset Button
Hidden Switch (with no Ident) that enables the
(Note - No Ident)
Processors and Remote Units to be reset.
Handset Fault
Will illuminate if a fault is detected with the Control
Unit handset.
System OK
Illuminates when no faults are detected.
Lamp Test /
Lamp Test - Press to check all front panel LEDs and
Fault Accept Button
buzzer operation.
Fault Accept - Press to accept a fault and silence the
fault buzzer.
N
: * If both the "Battery High" and "Battery Low" fault LEDs are
OTE
lit then the batteries are not connected.
OmniCare EVC System
Installation & Commissioning Manual
9