4.5 F

4.5.1 Introduction

4.5.2 Disabled Refuge Remote (BVOCECP)

OmniCare issue 1
UNCTIONAL
Remote Units can only be functionally tested after the Control
Panel has successfully completed the Commissioning Process.
If
s are to be re-addressed please refer to Section 5.1
Remote Unit
on page 65 for further details on re-addressing.
N
: To perform functional testing on Remote Units it will be necessary
OTE
to activate the Fire Panel input on the Control Panel.
Figure 4.4 — BVOCECP Remote Unit Front Panel Controls
1. Ensure the "SYSTEM OK" LED is flashing, and press the
"CALL" button.
Ensure the "Status" LED illuminates.
2. Both the Remote Unit and the Control Panel(s) will 'ring'.
The associated red LED on the Control Panel(s) will flash to
indicate activity at that Remote Unit location.
Check that when the Control Panel handset is lifted and the
zone is selected communication can be established.
N
: If only one Remote Unit is calling the Control Panel then that call
OTE
is automatically answered by lifting the handset.
T
R
ESTING
EMOTE
OmniCare EVC System
Installation & Commissioning Manual
U
NITS
55