4.5.5 Combined Remotes (BVOCRFC)

4.5.5.1 Disabled Refuge section of BVOCRFC
4.5.5.2 Fire Telephone section of BVOCRFC

4.5.6 Disabled Toilet Alarm (BVOCDTA)

58
N
: The Fire Telephone Remote Units are permanently enabled so it
OTE
is not necessary to activate the Fire Panel Input on the Control Panel to
perform a functional check.
The Disabled Refuge section does require the Fire Panel input to be
activated before a call can be made.
Refer to Section 4.5.2 for functional testing of the Disabled
Refuge sub-assembly.
N
: The volume control is shared by the Disabled Refuge and the Fire
OTE
Telephone and is adjusted while testing the Fire Telephone.
Refer to Section 4.5.4 for functional testing of the Fire Telephone
sub-assembly.
1. Ensure the "SYSTEM OK" LED is flashing on the
BVFREPEM.
2. Pull the Ceiling Pull Cord to activate the Toilet Alarm.
3. Ensure the Local Alarm is activated, and (if fitted) the Over
Door Beacon flashes.
4. Ensure the relevant Red LED on the Control Panel flashes to
indicate the Alarm.
5. Lift the Handset on the Control Panel and ensure an Alarm
Tone can be heard.
Ensure the Red LED on the Control Panel stops flashing, and
(if used) the "Help Acknowledge" indicator is illuminated at
the Toilet Alarm.
6. Press the "RESET" button on the Toilet Alarm controller to
cancel the alarm.
Ensure the Red LED on the Control Panel extinguishes.