Sfp+ Cable; Qsfp+ Cable - H3C S7508E-X Installation Manual

Hide thumbs Also See for S7508E-X:
Table of Contents

Advertisement

The optical interfaces on some cards have shielded covers. Remove the shielded covers before
using the optical interfaces. Optical interfaces must be installed with shielded covers when they are
not in use. Keep them safely.
Fiber connectors must be protected under safe and reliable outer packing, and be fitted with dust
caps. Fiber connectors must be installed with dust caps when they are not in use. Take care not to
scratch their end face. Replace the dust cap if it is loose or polluted.
Before connecting a fiber, use dust free paper and absolute alcohol to clean the end face of the
fiber connector. You can brush the end face only in one direction. You also need to brush the end
face of the other fiber connector.
Never bend or curve a fiber when connecting it. After a fiber is installed well, the bend radius must
be not less than 40 mm (the minimum dynamic bend radius is 20 D, and the minimum static bend
radius is 10 D. D indicates the outer diameter of fiber jackets).
If the fiber has to pass through a metallic board hole, the hole must have a sleek and fully filleted
surface. (The filleting radius must be not less than 2 mm.) When passing through a metallic board
hole or bending along the acute side of mechanical parts, the fiber must wear jackets or cushions.
Insert and remove a plug with care. Never exert a fierce force to the fiber or plug; otherwise the
plug may be damaged or the fiber may be broken. Never pull, press or extrude the fiber fiercely.
For the allowed maximum tensile load and crush load, see

SFP+ cable

You can use SFP+ cables to connect the SFP+ interfaces. SFP+ cables support the SFP+ standard and use
10 G SFP+ Cu standard cables.
Figure 46 SFP+ cable
(1) Connector

QSFP+ cable

You can use QSFP+ cables to connect the QSFP+ interfaces.
Table
(2) Pull latch
90
53.

Advertisement

Table of Contents
loading

Table of Contents