Emerson Rosemount 2051 Quick Installation Manual page 10

Pressure transmitter with 4-20 ma hart and 1-5 vdc hart low power protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents

Advertisement

Rosemount 2051
Figure 7. Wiring
Trim shield and insulate
Insulate Shield
Connect Shield Back
to the Power Supply
Ground
NOTE
Do not connect the powered signal wiring to the test terminals. Power could damage the test
diode in the test connection. Shielded twisted pair cable should be used for best results. Use
24 AWG or larger wire and do not exceed 5,000 feet (1500 meters).
4. Plug and seal unused conduit connections.
5. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower
than the conduit connections and the transmitter housing.
6. Replace the housing cover.
10
DP
Quick Installation Guide
00825-0100-4101, Rev CA
August 2009