Installation and maintenance work

These warnings are intended for all who work on the drive, motor cable or motor.
WARNING! Ignoring the following instructions can cause physical injury or death, or
damage to the equipment:
Note:
Safety instructions
Only qualified electricians are allowed to install and maintain the drive.
Never work on the drive, motor cable or motor when main power is applied.
After disconnecting the input power, always wait for 5 min to let the intermediate
circuit capacitors discharge before you start working on the drive, motor or
motor cable.
Always ensure by measuring with a multimeter (impedance at least 1 Mohm)
that:
1. voltage between drive input phases U1, V1 and W1 and the frame is close to
0 V.
2. voltage between terminals UDC+ and UDC- and the frame is close to 0 V.
Do not work on the control cables when power is applied to the drive or to the
external control circuits. Externally supplied control circuits may cause
dangerous voltages inside the drive even when the main power on the drive is
switched off.
Do not make any insulation or voltage withstand tests on the drive or drive
modules.
When reconnecting the motor cable, always check that the phase order is
correct.
The motor cable terminals on the drive are at a dangerously high voltage when
the input power is on, regardless of whether the motor is running or not.
The brake control terminals (UDC+, UDC-, R+ and R- terminals) carry a
dangerous DC voltage (over 500 V).
Depending on the external wiring, dangerous voltages (115 V, 220 V or 230 V)
may be present on the terminals of relay outputs RO1 to RO3 or on the optional
AGPS board (Prevention of Unexpected Start, ACS800-01/U1, ACS800-04/
04M, ACS800-11/U11, ACS800-31/U31).
ACS800-02 with enclosure extension: The main switch on the cabinet door
does not remove the voltage from the input busbars of the drive. Before working
on the drive, isolate the whole drive from the supply.
ACS800-01/U1, ACS800-04/04M, ACS800-11/U11, ACS800-31/U31: The
Prevention of Unexpected Start function does not remove the voltage from the
main and auxiliary circuits.