Planning The Electrical Installation; What This Chapter Contains; To Which Products This Chapter Applies; Motor Selection And Compatibility - ABB ACS800-04 Hardware Manual

Acs800 series
Hide thumbs Also See for ACS800-04:
Table of Contents

Advertisement

Planning the electrical installation

What this chapter contains

This chapter contains the instructions that you must follow when selecting the motor,
cables, protections, cable routing and way of operation for the drive system.
Note: The installation must always be designed and made according to applicable
local laws and regulations. ABB does not assume any liability whatsoever for any
installation which breaches the local laws and/or other regulations. Furthermore, if
the recommendations given by ABB are not followed, the drive may experience
problems that the warranty does not cover.

To which products this chapter applies

This chapter applies to the ACS800-01/U1, ACS800-11/U11, ACS800-31/U31,
ACS800-02/U2,
Note: All options described in this chapter are not available for all products. Check
the availability from section Type code on page 26.

Motor selection and compatibility

1. Select the motor according to the rating tables in chapter Technical Data. Use the
DriveSize PC tool if the default load cycles are not applicable.
2. Check that the motor ratings lie within the allowed ranges of the drive control
program:
• motor nominal voltage is 1/2 ... 2 · U
• motor nominal current is 1/6 ... 2 · I
ACS800-04/U4, and ACS800-07/U7 types up to -0610-x.
0 ... 2 · I
in scalar control. The control mode is selected by a drive parameter.
2hd
of the drive
N
of the drive in DTC control and
2hd
Planning the electrical installation
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-04mAcs800-u4

Table of Contents