100

Prevention of Unexpected Start: AGPS-21 board

Nominal input voltage
Input voltage range
(selected by jumper)
Nominal frequency
Current
Max. external fuse
Input connector X1
User connector 1, 2, 3
Output voltage
Nominal output current
X2 terminal block type
Ambient temperature
Relative humidity
Approvals

Ambient conditions

Installation site altitude
Air temperature
Relative humidity
Contamination levels
(IEC 60721-3-3, IEC 60721-3-
2, IEC 60721-3-1)
Atmospheric pressure
Vibration (IEC 60068-2)
Shock (IEC 60068-2-29)
Free fall
Technical data
115 VAC or 230 VAC
95...132 VAC (X3 on), 185...265 VAC (X4 on, default)
50/60 Hz
0.77 A at 115 V, 0.44 A at 230 V
16 A
2
3 × 2.5 mm
2
600 V, 25 A, 0.5...4 mm
24 V + 0.5 V
1.7 A (50 °C, 122 °F)
JST B3P-VH
0...50 °C (32...122 °F)
30...90%, no condensation allowed
CE, C-UL US listed
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Operation
installed for stationary use
0 to 4000 m (13123 ft) above
sea level [above 1000 m
(3281 ft), see section
Derating]
-15 to +50 °C (5 to 122 °F).
No frost allowed. See
section Derating.
5 to 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
No conductive dust allowed.
Boards without coating:
Chemical gases: Class 3C1
Solid particles: Class 3S2
Boards with coating:
Chemical gases: Class 3C2
Solid particles: Class 3S2
70 to 106 kPa
0.7 to 1.05 atmospheres
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
2
2
max. 7 m/s
(23 ft/s
)
(13.2 to 100 Hz) sinusoidal
Not allowed
Not allowed
(20...12 AWG)
Storage
in the protective package
-
-40 to +70 °C (-40 to
+158 °F)
Max. 95%
Boards without coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards with coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
70 to 106 kPa
0.7 to 1.05 atmospheres
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
2
2
max. 7 m/s
(23 ft/s
(13.2 to 100 Hz) sinusoidal
2
Max. 100 m/s
(330 ft./s
11 ms
100 mm (4 in.) for weight
over 100 kg (220 lb)
Transportation
in the protective package
-
-40 to +70 °C (-40 to
+158 °F)
Max. 95%
Boards without coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Boards with coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
60 to 106 kPa
0.6 to 1.05 atmospheres
Max. 3.5 mm (0.14 in.)
(2 to 9 Hz),
2
)
max. 15 m/s
(49 ft/s
(9 to 200 Hz) sinusoidal
2
2
),
Max. 100 m/s
11 ms
100 mm (4 in.) for weight
over 100 kg (220 lb)
2
)
2
(330 ft./s
),