Additional Indications; Correction Procedures; Changing And Setting The Password; Identifying Ied Application Problems - ABB REC650 Commissioning Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

Section 8
Troubleshooting
8.2.3
8.3
8.3.1
8.3.2
96
internal fault signals can also be checked via the LHMI in Main menu/Diagnostics/
IED status/General.
When a fault appears, record the fault indication message and state it when
ordering service.
Table 4:
Warning indications
Warning indication
Warning
IEC 61850 Error
Warning
DNP3 Error

Additional indications

The additional indication messages do not activate internal fault or warning.
The messages are listed in the LHMI menu under the event list. The signal status
data is found under the IED status and in the internal event list.
Table 5:
Additional indications
Warning indication
Time Synch Error
BATTERY1 Error
Settings Changed
Setting Groups Changed

Correction procedures

Changing and setting the password

The password can only be set with PCM600.
For more information, see PCM600 documentation.

Identifying IED application problems

Navigate to the appropriate menu in the LHMI to identify possible problems.
Additional information
IEC 61850 has not succeeded
in some actions such as
reading the configuration file,
startup etc.
Error in DNP3 communication.
Additional information
Source of the time synchronization is lost or time
system has made a time reset.
Auxiliary power is disconnected.
Settings have been changed.
Setting group has been changed.
1MRK 511 248-UEN -
Commissioning Manual

Advertisement

Table of Contents
loading

Table of Contents