Setting up the PC to access the IED via a network
This task depends on the used LAN/WAN network. PC and IED must belong to the
same subnetwork.

Writing an application configuration to the IED

Ensure that the IED includes the correct application configuration
according to project specifications.
The application configuration is created using PCM600 and then written to the
IED. Establish a connection between PCM600 and the IED when an application
configuration must be written to the IED.
When writing an application configuration to the IED, the IED is automatically set
in the configuration mode. When the IED is set in the configuration mode, all
functions are blocked. The red Trip LED on the IED flashes, and the green Ready
LED is lit while the IED is in the configuration mode. When the writing procedure
has completed, the IED is automatically set into normal mode.
After writing an application configuration to the IED, the IED makes an
application restart or a complete IED restart, when necessary.