ABB REC650 Commissioning Manual page 99

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 248-UEN -
Commissioning Manual
Commissioning and maintenance of the fault clearing system
Trip circuit check
When the protection IED undergoes an operational check, a tripping pulse is
normally obtained on one or more of the output contacts and preferably on the test
switch. The healthy circuit is of utmost importance for the protection operation. If
the circuit is not provided with a continuous trip-circuit supervision, it is possible
to check that circuit is really closed when the test-plug handle has been removed by
using a high-ohmic voltmeter and measuring between the plus and the trip output
on the panel. The measurement is then done through the tripping magnet of the
circuit breaker and therefore the complete tripping circuit is checked.
Note, that the breaker must be closed.
Please observe that the test system does not have its built-in
security during this test. If the instrument should be set on Amp
instead of Volts, the circuit breaker naturally is tripped, therefore,
greatest care is necessary.
Trip circuit from trip IEDs to circuit breaker is often supervised by trip-circuit
supervision. It can then be checked that a circuit is healthy by opening tripping
output terminals in the cubicle. When the terminal is opened, an alarm shall be
achieved on the signal system after a delay of some seconds.
However, remember to close the circuit directly after the test and
tighten the terminal carefully!
Measurement of service currents
After a maintenance test it is recommended to measure the service currents and
service voltages recorded by the protection IED. The service values are checked on
the local HMI or in PCM600. Ensure that the correct values and angles between
voltages and currents are recorded. Also check the direction of directional
functions such as Distance and directional overcurrent functions.
For transformer differential protection, the achieved differential current value is
dependent on the tap changer position and can vary between less than 1% up to
perhaps 10% of rated current. For line differential functions, the capacitive
charging currents can normally be recorded as a differential current.
The zero-sequence current to earth-fault protection IEDs should be measured. The
current amounts normally very small but normally it is possible to see if the current
circuit is "alive".
The neutral-point voltage to an earth-fault protection IED is checked. The voltage
is normally 0.1 to 1V secondary. However, voltage can be considerably higher due
Section 7
91

Advertisement

Table of Contents
loading

Table of Contents