ABB REC650 Commissioning Manual page 53

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 248-UEN -
Commissioning Manual
The I Dir (I
cos(Angle)) function activates the START and STDIRIN output.
0
Measure with angles j = RCADir +/- 45° that the measuring element
3.
cos (RCADir - j) = I
operates when I
0
4.
Compare the result with the set value.
Take the set characteristic into consideration, see figure
5.
Measure the operate time of the timer by injecting a current two times the set
INcosPhi> value and the polarizing voltage 1.2 · UNRel>.
=
×
Tinv
kSN Sref
/ 3
IECEQUATION2402 V1 EN
6.
Compare the result with the expected value.
The expected value depends on whether definite or inverse time was selected.
7.
Set the polarizing voltage to zero and increase until the boolean output signal
UNREL is activated, which is visible in the Application Configuration in
PCM600 when the IED is in online mode. Compare the voltage with the set
value UNRel>.
8.
Continue to test another function or complete the test by setting the test mode
to Off.
IEC06000650 V2 EN
Figure 9:
Characteristic with ROADir restriction
cos(+/-45) = INcosPhi>.
0
( )
j
×
I
cos
0
test
3I
0
j
3 ×
j
I
cos
0
ROADir
Section 6
Testing functionality
9
and figure 10.
o
=
RCADir
0
Operate area
-
=
3
U
U
0
ref
IEC06000650_2_en.vsd
(Equation 1)
45

Advertisement

Table of Contents
loading

Table of Contents