Warnings; Additional Indications; Correction Procedures; Resetting The Configuration - ABB Relion 630 Series Commissioning Manual

Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

Section 5
Troubleshooting
5.2.2
5.2.3
5.3
5.3.1
32

Warnings

The warning message associated with the fault is found in the internal event list in
the LHMI menu Main menu/Monitoring/Internal events. The message includes
the date, time, description and signal state for the fault. The current status of the
internal fault signals can also be checked via the LHMI in Main menu/Monitoring/
IED status.
When a fault appears, the fault indication message is to be recorded and stated
when ordering service.
Table 4:
Warning indications
Warning indication
Warning
IEC 61850 Error
Warning
DNP3 Error

Additional indications

The additional indication messages do not activate internal fault or warning.
The messages are listed in the LHMI menu under the event list. The signal status
data is found under the IED status and in the internal event list.
Table 5:
Additional indications
Warning indication
Time Synch Error
BATTERY1 Error
BATTERY2 Error
Settings Changed
Setting Groups Changed

Correction procedures

Resetting the configuration

The configuration is reset with PCM600.
For more information, see PCM600 documentation.
Additional information
IEC 61850 has not succeeded in some
actions such as reading the configuration
file, startup etc.
Error in DNP3 communication.
Additional information
Source of the time synchronization is lost
or time system has made a time reset.
BATTERY1 Error status.
BATTERY2 Error status.
Settings have been changed.
Setting group has been changed.
1MRS756801 A
630 series
Commissioning Manual