Section 6 Testing Functionality; Testing Disturbance Report; Introduction; Disturbance Report Settings - ABB REC650 Commissioning Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 248-UEN -
Section 6
6.1
6.1.1
6.1.2
6.2
Commissioning Manual
Testing functionality

Testing disturbance report

Introduction

The following sub-functions are included in the disturbance report function:
Disturbance recorder
Event list
Event recorder
Trip value recorder
Indications
If the disturbance report is set on, then its sub-functions are also set up and so it is
not possible to only switch these sub-functions off. The disturbance report function
is switched off (parameter Operation = Off) in PCM600 or the local HMI under
Main menu/Settings/IED Settings/Monitoring/Disturbance report/
1:DRPRDRE.

Disturbance report settings

When the IED is in test mode, the disturbance report can be made active or
inactive. If the disturbance recorder is turned on during test mode, recordings will
be made. When test mode is switched off all recordings made during the test
session are cleared.
Setting OpModeTest for the control of the disturbance recorder during test mode
are located on the local HMI under Main menu/Settings/IED Settings/
Monitoring/Disturbance report/1:DRPRDRE.
Identifying the function to test in the technical
reference manual
Use the technical manual to identify function blocks, logic diagrams, input and
output signals, setting parameters and technical data.
Section 6
Testing functionality
39