Indication Messages; Internal Faults; Warnings - ABB REC650 Commissioning Manual

Relion 650 series bay control
Hide thumbs Also See for REC650:
Table of Contents

Advertisement

1MRK 511 248-UEN -
8.2
8.2.1
8.2.2
Commissioning Manual

Indication messages

Internal faults

When the Ready LED indicates an internal fault by flashing, the message
associated with the fault is found in the internal event list in the LHMI menu Main
menu/Diagnostics/Internal events. The message includes the date, time,
description and signal state for the fault. The internal event list is not updated
dynamically. The list is updated by leaving the Internal events menu and then
selecting it again. The current status of the internal fault signals can also be
checked via the LHMI in Main menu/Diagnostics/IED status.
Different actions are taken depending on the severity of the fault. After the fault is
found to be permanent, the IED stays in internal fault mode. The IED continues to
perform internal tests during the fault situation.
When a fault appears, the fault indication message is to be recorded and stated
when ordering service.
Table 3:
Internal fault indications
Fault indication
Internal Fault
Real Time Clock Error
Internal Fault
Runtime Exec. Error
Internal Fault
SW Watchdog Error
Internal Fault
Runtime App Error
Internal Fault
File System Error
Internal Fault
TRM-Error
Internal Fault
COM-Error
Internal Fault
PSM-Error

Warnings

The warning message associated with the fault is found in the internal event list in
the LHMI menu Main menu/Diagnostics/Internal events. The message includes
the date, time, description and signal state for the fault. The current status of the
Section 8
Troubleshooting
Additional information
Hardware error with the real time clock.
One or more of the application threads
are not working properly.
This signal will be activated when the
terminal has been under too heavy
load for at least 5 minutes.
One or more of the application threads
are not in an expected state.
A file system error has occurred.
A TRM card error has occurred. The
instance number is displayed at the
end of the fault indication.
A COM card error has occurred. The
instance number is displayed at the
end of the fault indication.
A PSM card error has occurred. The
instance number is displayed at the
end of the fault indication.
95