Additional Indications; Correction Procedures; Changing And Setting The Password; Identifying Ied Application Problems - ABB RET650 Series Commissioning Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650 Series:
Table of Contents

Advertisement

Section 9
Troubleshooting
9.2.3

Additional indications

The additional indication messages do not activate internal fault or warning.
The messages are listed in the LHMI menu under the event list. The signal status data is found
under the IED status and in the internal event list.
Table 6:
Warning indication
Time Synch Error
Settings Changed
Setting Groups Changed
9.3

Correction procedures

9.3.1

Changing and setting the password

The password can only be set with PCM600.
9.3.2

Identifying IED application problems

Navigate to the appropriate menu in the LHMI to identify possible problems.
Check that the function is on.
Check that the correct setting group (1 to 4) is activated.
Check the blocking.
Check the mode.
Check the measurement value.
Check the connection to trip and DFR functions.
Check the channel settings.
9.3.2.1

Inspecting the wiring

The physical inspection of wiring connections often reveals the wrong connection for phase
currents or voltages. However, even though the phase current or voltage connections to IED
terminals might be correct, wrong polarity of one or more measurement transformers can cause
problems.
Check the current or voltage measurements and their phase information from Main menu/
Measurements/Analog primary values or Analog secondary values.
Check that the phase information and phase shift between phases is correct.
Correct the wiring if needed.
94
Additional indications
For more information, see PCM600 documentation.
© Copyright 2013 ABB. All rights reserved
Additional information
Source of the time synchronization is lost or time
system has made a time reset.
Settings have been changed.
Setting group has been changed.
Transformer protection RET650
1MRK 504 136-UUS B
GUID-69561C77-50E8-45E2-B8AC-80116222B5B9 v3.1.1
GUID-D3FA85BA-1E36-4F8B-BD71-85C7AC46A0B4 v1
GUID-D8E1AECF-1FD8-4996-A447-948B52EAD0C2 v5
GUID-665B75A6-A074-4A03-ADF1-3D0FAD198E61 v5