4. Operation

Display Point

Display Point operations display addressable device status on the LCD display. After the status of the
device displays, press the Up arrow key to display the status of the next highest addressable device or
press the Down arrow key to display the status of the previous addressable device. The sequence of
display point is 1) Detector points 01-99, 2) Module points 01-99, 3) NAC bell circuits 01 and 02, 4)
System Parameters, and 5) Zones 1-56.
A typical Read Status display is as follows:
In the preceding display:
If the point is not installed, a Read Status command to that point will result in a "Not Installed" message
on the display.
Read History
The control panel provides a history file that can store up to 500 events, such as Point Status, System
Troubles, and Acknowledge/Step, Alarm Silence, Drill and System Reset key presses. All history
events are recorded with the time and date.
History events are stored in volatile memory, therefore, removal of primary AC power and secondary
battery power will clear the history buffer. To clear the History file without removing power, see"Clear
History" on page 52. To view events in the history file, use the Up and Down arrow keys to step through
the events.

Print Program

You can use Print Program function to print all user-programmed options, including device types,
software zone assignments, system parameters, and current system status.
Note: For instructions on connecting a printer, refer to "Printer and PC Interface" on page 38.

Print History

You can use Print Program function to print the entire 500-event history file.
Note: For instructions on connecting a printer, refer to "Printer and PC Interface" on page 38.
70
Technical Manuals Online! - http://www.tech-man.com
NORMAL SMOKE DET P01
WEST HALLWAY
• NORMAL is the present status (could be ALARM, TRBL_#, DISABL, etc.)
• SMOKE DET is the device type; P indicates that this is a photoelectric detector and 01 is the
device address
• WEST HALLWAY is the custom label programmed for this device
• MZ56 is the assigned software zone
Read Status
MZ56
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002