Print Detector Data - Notifier AFP-100 Instruction Manual

Intelligent fire panel
Table of Contents

Advertisement

Read Status
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
Technical Manuals Online! - http://www.tech-man.com

Print Detector Data

An addresssable smoke detector's ability to detect smoke can change over time as a result of component
deterioration due to environmental contaminants and dirt. Use the Print Detector Data function to print
the current sensitivity of each addressable smoke detector in the system.
To print each addressable smoke detector's (sensitivity) data, press '3' then ENTER while viewing the
Print screen. A printout similar to the sample shown in Figure 24 will be generated to an optional printer
connected to the FACP.
*******************************DETECTOR DATA********************************
DEVICE TYPE
DEVICE TYPE
DEVICE TYPE
DEVICE TYPE
SMOKE DET P01
SMOKE DET P02
SMOKE DET I03
SMOKE DET T04
Figure 24 Sample Detector Data Printout
Note: If a printer is not available, it is possible to store Detector Data information by using the HyperTerminal feature
available on most personal computers running the Windows® operating system. Any settings which are configured in
this feature must reflect the printer settings detailed in "Printer Configuration" on page 39. Refer to the Windows®
Manual for information on the HyperTerminal feature.
The Chamber Reading
The Chamber Reading should be within the ranges indicated in Table 12. If the addressable smoke
detector's Chamber Reading is not within the acceptable range, clean the detector, regenerate Detector
Data, and recheck the Chamber Reading. If the reading is still not within the acceptable range, replace
the detector immediately.
Model
Device Type
FSI-751
Low-Profile Intelligent Ionization Smoke Detector
FSP-751
Low-Profile Intelligent Photoelectric Smoke Detectors
FSP-751T
HPX-751
Analog Addressable Smoke Detectors
FSD-751P
Intelligent Photoelectric Duct Detectors
FSD-751RP
FST-751
Intelligent Thermal Detectors
FST-751R
Table 12 Acceptable Ranges for Addressable Detectors
CHAMBER READING
CHAMBER READING
CHAMBER READING
CHAMBER READING
947
03:52P Fri 09/28/01
908
03:52P Fri 09/28/01
968
03:52P Fri 09/28/01
1000
03:52P Fri 09/28/01
4. Operation
TIME/DATE
TIME/DATE
TIME/DATE
TIME/DATE
Acceptable Range
270 - 1400
500 - 1400
500 - 1400
500 - 1400
600 - 1800