Siemens SITRANS P DS III Operating Instructions Manual page 61

Pressure transmitter with profibus pa
Hide thumbs Also See for SITRANS P DS III:
Table of Contents

Advertisement

Figure 4-4
The turning range for transmitters for differential pressure and flow rate, absolute pressure
from the differential pressure series and level is identified in a similar manner.
Procedure
NOTICE
Damage to the ribbon cable
If the transmitter enclosure is rotated against the measuring cell, this can damage the
ribbon cable (sensor connection to the electronics).
• Comply with the specified range of rotation
1. Loosen the retaining screw
2. Turn the electronic housing against the measuring cell. Follow the marked turning range
3. Tighten the retaining screw (torque: 3.4 to 3.6 Nm).
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
Turning range
Retaining screw
Orientation mark
Example: turning range of transmitters for pressure and absolute pressure from the
gauge pressure series
while doing so.
4.6 Turing the measuring cell against housing
as detailed.
(Allen screw 2.5 mm).
Installing / mounting
61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents