Functional safety
8.7 PROFIsafe
8.7.4

Preconditions

CPU
The CPU must be capable of operating in fail-safe mode to be able to communicate with
PROFIsafe devices.
These F-CPUs are contained in the catalog ST 70, SIMATIC S7.
Electronic Device Description (EDD):
Operate your application in conjunction with the EDD and GSD of SITRANS P, series DSIII
PA PROFIsafe in the following system environment:
● with EDD version 01.02.01-53 with GSD "SI0180A6.GSD revision 1.03"
– PCS 7 V7.0 and F systems V5.2SP4 with library Failsafe Blocks (V1_2) or
– PCS 7 V7.0 and F systems V6.0 with library Failsafe Blocks (V1_2) or
● EDD version 01.02.02 or higher with GSD "SI0180A6.GSD revision 1.04" with
PCS 7 V7.0 SP1 and F systems V6.0 with library S7 F Systems Lib V1_3
● EDD version 01.02.03 or higher with GSD "SIEM8170.GSD revision 1.0" with
PCS7 V7.1 SP3 and F systems V6.1 with libraryS7 F Systems Lib V1_4
Note
With this EDD, the "PROFIBUS Ident number" parameter can be set to manufacturer-
specific (3.01), PROFIsafe V1/V2
PROFIsafe device
For safety reasons, the PROFIsafe device ships with default settings. This means
PROFIsafe is deactivated. You activate PROFIsafe with the PROFIsafe commissioning.
Technical requirements for PROFIsafe:
● SIMATIC PDM HF1
● EDD from 01.02.01
● Firmware from 301.02.01
8.7.5

PROFIsafe Configuration

For safety reasons, the PROFIsafe device ships with default settings.
Requirement
Before you commission the PROFIsafe device, configure it, for example in STEP 7.
138
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07