gauge pressure input, with flush mounted diaphragm
Measured variable
Span (continuously
adjustable) or measuring
range, max. operating
pressure and max. test
pressure
Lower measuring limit
Measuring cell with
•
silicone oil filling
Measuring cell with
•
inert liquid
Measuring cell with
•
neobee
Upper measuring limit
Absolute pressure input, with flush-mounted diaphragm
Measured variable
Span (continuously
adjustable) or measuring
range, max. operating
pressure and max. test
pressure
SITRANS P DS III with PROFIBUS PA
Operating Instructions, 06/2013, A5E00053276-07
HART
Gauge pressure
Span
Maximum
operating
pressure
MAWP (PS)
0.01 ...
4 bar g
1 bar g (0.15
(58 psi g)
... 14.5 psi g)
0.04 ...
7 bar g
4 bar g (0.58
(102 psi g)
... 58 psi g)
0.16 ...
21 bar g
16 bar g (2.3
(305 psi g)
... 232 psi g)
0.6 ...
67 bar g
63 bar g (9.1
(972 psi g)
... 914 psi g)
100 mbar a (1.45 psi a)
100 mbar a (1.45 psi a)
100 mbar a (13.05 psi a)
100% of maximum span
HART
Absolute pressure
Span
Maximum
operating
pressure
MAWP (PS)
43 ...
2.6 bar a
1300 mbar a
(37.7 psi a)
(17 ...
525 inH
O)
2
160 ...
10 bar a
5000 mbar a
(145 psi a)
(2.32 ...
72.5 psi a)
PROFIBUS PA and FOUNDATION Fieldbus
Maximum test
Measuring
pressure
range
6 bar g
1 bar g
(87 psi g)
(14.5 psi g)
10 bar g
4 bar g
(145 psi g)
(58 psi g)
32 bar g
16 bar g
(464 psi g)
(232 psi g)
100 bar g
63 bar g
(1450 psi g)
(914 psi g)
100% of max. measuring range
PROFIBUS PA and FOUNDATION Fieldbus
Maximum test
Measuring
pressure
range
10 bar a
1.3 bar a
(145 psi a)
(18.9 psi a)
30 bar a
5 bar a
(435 psi a)
(72.5 psi a)
Technical data
13.2 Input point
Maximum
Maximum test
operating
pressure
pressure
4 bar g
6 bar g
(58 psi g)
(87 psi g)
7 bar g
10 bar g
(102 psi g)
(145 psi g)
21 bar g
32 bar g
(305 psi g)
(464 psi g)
67 bar g
100 bar g
(972 psi g)
(1450 psi g)
Maximum
Maximum test
operating
pressure
pressure
2.6 bar a
10 bar a
(37.7 psi a)
(145 psi a)
10 bar a
30 bar a
(145 psi a)
(435 psi a)
193