Mitsubishi Electric QD62 User Manual page 63

Q series high-speed counter module
Hide thumbs Also See for QD62:
Table of Contents

Advertisement

5 BASIC USAGE
5 - 8
(2) Output status setting during a CPU stop error
The output status (clear/hold) can be set for the external output signal when a
CPU stop error occurs.
The output status is set using the GX Developer I/O assignment.
See Section 4.5 for details on the I/O assignment setting method.
(3) Coincidence detection interrupt function
The coincidence detection interrupt function allows making an interrupt request to
a programmable controller CPU at the time of coincidence detection to start the
interrupt program.
(When the programmable controller CPU is a Q00J/Q00/Q01CPU, use function
version B or later.)
(a) With the MELSEC-Q series intelligent function module, each module can
have up to 16 points of interruption factors (SI).
The QD62 (E/D) has 4 points of interrupt factors corresponding to the
coincidence outputs shown below.
SI No.
0
1
2
3
4 to 15
Timing of interrupt signal generation
I/O signal
Internal processing
Program controller CPU program processing
(b) Select "PLC parameter" - "PLC system" - "Intelligent function module setting"
- "Interrupt pointer settings" to set the interrupt factors (SI) of the QD62(E/D)
and interrupt pointers of the PLC CPU.
1) CPU side [Interrupt pointer start No.]
Set the start interrupt pointer number of the programmable controller
CPU.
Setting range: 50 to 255
2) PLC side "Interrupt pointer No. of module"
Set the number of interrupt factors (SI).
Setting range: 1 to 4
Channel 1: Coincidence detection for coincidence output point No. 1
Channel 1: Coincidence detection for coincidence output point No. 2
Channel 2: Coincidence detection for coincidence output point No. 1
Channel 2: Coincidence detection for coincidence output point No. 2
Counter value
coincidence
{X02/X06(X09/X0D)}
Coincidence signal
reset command
{Y00/Y07(Y08/Y0F)}
Interrupt request
Clear interrupt request
Interruption factor
Vacant
Interrupt program
processing
MELSEC-Q
5 - 8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qd62eQd62d

Table of Contents