3.2.3 Parameter Setting

Unit parameters can be set in unit On or Off status.
(1) Long press MODE and SWING button for 5s and the temperature zone displays "C00";
long press MODE and SWING button for another 5s to enter the interface of setting wired
controller parameters. "P00" is displayed in temperature zone;
(2) Press "
parameter setting. At that time, parameter value is blinking. Press
adjust the parameter value and press SWING button to finish setting.
(3) Press SWING button to return to last step until exists setting parameters.
The parameter setting list is as following:
Parameter
Parameter
code
name
Set master
P10
indoor unit
Set infrared
P11
receiver of
wired controller
Set address of
P13
wired controller
Set quantity of
P14
group control
indoor units
Set unit of
P16
temperature
Set static
pressure of
P30
indoor fan
motor
" or "
" button to select parameter code. Press MODE button to enter
Table 3.2 Parameter setting list
Parameter range
00: do not
change
current
master/slave
state of indoor
unit
01: set current
indoor unit as
master indoor
unit
00: forbidden
01: activated
01: master wired
controller
02: slave wired
controller
00: forbid this
function
01-16: indoor unit
quantity
00:Celsius
01:Fahrenheit
01-09: static
pressure level of
indoor fan motor
Default
value
When set the corresponding indoor unit
of wired controller as master indoor
00
unit, MASTER" icon will be bright after
finishing setting.
It can be set only through master wired
controller.
When infrared receiver of wired
01
controller is forbidden, the wired
controller can't receive the signal from
remote controller and it is operated
through buttons.
When two wired controllers control one
indoor unit (or several indoor units), the
addresses of the two wired controllers
01
should be different. Assistant wired
controller (02) is without unit parameter
setting function except setting its
address.
Set the corresponding value according
01
to the connected indoor unit quantity.
00
There are two kinds of static pressure
level:
5 levels: 03, 04, 05, 06, 07
9 levels: 01, 02, 03, 04, 05, 06, 07, 08,
09
05
Static pressure level range is different
for different models; the wired controller
will automatically select static pressure
level range
according to the model of indoor unit.
15
"
" or "
"
button to
Note
of
indoor fan motor