FIGURE 47: BMS-Ready Control AM Style Units (2010 - 2010B)
L3
3 PHASE ONLY
L2
L1
FUSABLE DISCONNECT
FUSES BY OTHERS
BREAKER
3 AMP
1
1A
7
LOW PRES.
SWITCH
HI TEMP
0.3" W.C.
LIMIT
HLS
8
C
NO
NC
MANUAL
RESET
7
5
6
9C
7
24
3
UV
F
13
SCANNER
G
14
PRIMARY
RM7897C
IGNITION
CLIP JR2
CONTROL
FOR 2020 - 2030
THREE POSITION DIP
SWITCH ON SC11-B
4-20mA
ALL POSITIONS
3
O
ON
2
O
1
O
ON
OFF
T1 TRANSFORMER
PRIMARY CONNECTION
H1 - 460 USE 1.6 AMP BREAKER
H2 - 230 USE 3.0 AMP BREAKER
H3 - 208 USE 4.0 AMP BREAKER
H4 - COMMON
H4
H1
H2
H3
X1
X2
120vac
R1
3A
FAN
R2
BURNER
HI PRES.
SWITCH
1.4" W.C.
8A
C
NC
9
9A
9B
20
8
11
UV
SCANNER
10
10
2
2
PRIMARY
IGNITION
9
12
CONTROL
TEMP CONTROL
AMPLIFIER
SC11-B
6
5
0-10 VDC
ALL POSITIONS
OFF
40
41
4-20MA Input
Signal
OR 0-10VDC
Signal
SET DIP SWITCH
BEFORE CONNECTING POWER!
WIRE CONNECTIONS
DDC CONTROL TO CONTROL PANEL
1, 1A, 40, 41
42, 43, 44, 45
46, 47, 60, 61
M1
OL
MTR
BREAKER
T1
250VA
3B
3C
3D
M1
DM
4
COM
V+ OR
I+
T1
MODULATING DAMPER
MOTOR M9184D1021
WITH Q7230A INTERFACE
3
20
8
9C
11
6
7
10
10
4
24
F
2
13
G
9
12
14
RM7890A
CLIP JR2
15
4
3
2
1
48
49
MODULATING
REGULATING
VALVE MRV
SECTION 17: E
BLOWER
MOTOR
2
M1-OL
M1
MOTOR STARTER
MODULATING
DAMPER MOTOR
61
ADJUSTING OUTSIDE/
"-" SIGNAL
RETURN AIR RATIO
60
USE V+ WHEN 0-10VDC
"+" SIGNAL
SIGNAL IS REQUIRED
USE I+ WHEN 4-20MA
2
T2
SIGNAL IS REQUIRED
PV
PILOT VALVE
SP
T2
IGNITION
TRANSFORMER
R3
BURNER LOCKOUT
LIGHT (FLAME FAILURE)
120VAC
IGNITION
CONTROL
SSOV
SAFETY SHUTOFF
VALVE
T3
20VA
24VAC
X1
X2
16
RELAY R1 AND R2 VOLTAGE IS
SPECIFIED BY CONTRACTOR CAN
BE 120VAC, 24VAC, OR 24VDC
42
43
R1
COIL CONN BY OTHERS
44
45
R2
COIL CONN BY OTHERS
R3
46
47
BURNER LOCKOUT CONTACT
CONN BY OTHERS
LECTRICAL