Rapid 2005 Installation, Operation & Service Manual page 49

Direct, gas-fired, industrial air handler
Table of Contents

Advertisement

Step 11.3.5
Attach the remaining filter rails with four TEK
self-tapping screws, two on each side. Ensure
that the rails face into the filter section.
NOTE: For easier installation, the filter section
may be mounted to the air handler at this point,
prior to the addition of filters and access door.
Refer to Page 43, Section 11.5 for installation
instructions.
Step 11.3.6
Description
Filter Rail
TEK Screw
Load filters into the filter section.
Check that each filter in in the proper
orientation.
For permanent aluminum mesh
filters: Verify the arrow on the side of
the filter points in the direction of the
airflow.
For disposable polyester filters:
Verify the white side is facing the inlet
and the blue side is facing the
discharge end.
The end rows of filters need to be
installed first.
NOTE: When the filter section is
installed on the air handler, the top of
one row of filters will support the
bottom of the above row.
Description
Permanent Aluminum Mesh Filters
Disposable Polyester Filters
SECTION 11: F
S
ILTER
ECTION
Part Number
13X05030
13404
Part Number
20629 and/or 20628
23628/23631
39 of 147