Rapid 2005 Installation, Operation & Service Manual page 50

Direct, gas-fired, industrial air handler
Table of Contents

Advertisement

B-S
I
, O
ERIES
NSTALLATION
PERATION AND
Step 11.3.7
Spacers
Hinge
Duct
Liner
Door Panel
Door Panel
Bolt
Washer
Description
Gasket Material
Filter Access Door
Hinge
10-24 x ½" Bolt
10-24 Nut
Hinge Spacers
10-24 X ¾" Bolt
¼-20 Grip-Nut
¼" Washer
¼-20 Bolt
Push-Nut
40 of 147
S
M
ERVICE
ANUAL
Filter Section
On right panel, apply provided gasket material to the filter access
Panel
opening.
Attach filter access door with two hinges.
Attach the hinges to the door using three 10-24 x 1/2" bolts and
10-24 nuts. Attach the hinge to the filter section right panel using
three 10-24 x 3/4" bolts and 10-24 nuts. Use four hinge spacers
between the hinge and the right panel to keep the hinge aligned.
Press the ¼-20 grip-nuts into each of the three square cut outs in
the filter section right panel on the opposite side of the filter access
opening from the hinges.
Place a ¼" washer on a ¼-20 bolt and insert it into one of the three
bolt holes on the door panel. Place a push-nut on to the bolt from
the inside of the door panel to keep the bolt from being separated
from the door panel when it is open. Repeat for the other two bolt
holes. Secure the door in the closed position by threading the
three bolts in the door panel to the grip-nuts on the filter section
Gasket
right panel.
On the inlet of the filter section, rivnuts (P/N 91120106) are factory
Gasket
installed. With additional 3/8" hardware (P/N 20515 and
P/N 20517) the filter section can be installed on the inlet of the
unit. See Page 43, Section 11.5 for additional information on filter
section installation.
Grip Nut
Push Nut
Filter Box
Panel
Part Number
13205035
13X05025
20500
27000
20698
13205032
21699
20499
20503
20504
20505
Right Panel
Hinges
Bolt Holes

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

201020302010b2020

Table of Contents