Rapid 2005 Installation, Operation & Service Manual page 61

Direct, gas-fired, industrial air handler
Table of Contents

Advertisement

Step 12.2.10
Description
Drip Rail
TEK Screws
Attach drip rail to each side using five TEK self-tapping screws for each drip rail. Ensure that the drip
rails are positioned above the filter clips (where applicable), using the provided holes in the sidewall
panels. Apply caulk to the drip rails before attaching to the side panels.
NOTE: Double sided filter rails or snap fasteners are not required for inlet hood with moisture limiter.
For inlet hoods with permanent aluminum mesh filters, continue to step 12.2.11.
For inlet hoods with birdscreen, no filters, the instructions end here.
For inlet hoods with moisture limiter, continue to step 12.2.12.
Step 12.2.11
Description
Permanent Aluminum Mesh Filter
Load filters into the inlet hood, checking to see that each filter is in the proper orientation by
verifying that the arrow on the side of the filter points in the direction of air flow. All of the arrows
should be pointing towards the air handler when installed in the proper orientation. Once filters are
installed, close filter clips installed previously (See Page 50, Step 12.2.8) to hold filters in place.
For inlet hoods with permanent alumimum mesh filters the instructions end here.
Drip Rail
Part Number
13505092
13404
Size
Part Number
in
20 x 20 x 1
20628
cm 50.8 x 50.8 x 2.5
Filter
SECTION 12: I
H
NLET
OOD
51 of 147