General Information - AEMC 6417 User Manual

Clamp-on ground resistance tester
Hide thumbs Also See for 6417:
Table of Contents

Advertisement

6.1.2.2 Measurement Results
First Screen:
Once the measurement has stabilized, the
display shows the first screen, which indicates:
- The leakage current.
- The loop impedance referenced to the
chosen frequency.
The impedance is measured only if the leakage
current is less than 10A. In the 10 to 40A range,
only the current is displayed; the NOISE symbol
blinks and the impedance is replaced by dashes.
Second Screen:
Press ► to display the second screen, which
indicates the contact voltage (product ZxI).
Third Screen:
Press ► to display the third screen, which
indicates the values of R and L. The loop
inductance and loop resistance are displayed.
When the inductive component is negligible* with
respect to the resistive component, the symbol
R=Z is displayed, and only the impedance is
displayed; the inductance is replaced by dashes.
* R > 25W or R[W] / L[H] > 10

6.1.3 General Information

This information is displayed in both Standard and Advanced modes.
PRODUCT ZxI GREATER THAN 50V
- The blinking NOISE symbol is displayed.
- The impedance blinks.
- The hazardous voltage symbol blinks.
Clamp-on Ground Resistance Tester Model 6417
uality Products Online at:
5
GlobalTestSupply
www.
Figure 6-2
Figure 6-3
Figure 6-4
Figure 6-5
.com
sales@GlobalTestSupp
31

Advertisement

Table of Contents
loading

Table of Contents