6.1 Rotary Position W+A
6.1.1 Standard Mode
Selection of Standard mode is performed in the SET-UP (see § 4.4, menu #9).
In Standard mode, only one measurement screen is available. The clamp
measures the loop impedance (W) (at the fixed frequency of 2083Hz) and the
leakage current.
NOTE: Since the measurement frequency is audible, the operator hears a beeping
signal. This is neither an operating fault nor an alarm, and it cannot be eliminated.
This audible signal is amplified by the presence of current in the loop.
The alarm thresholds can be configured as desired (see § 4.4, menus #4, #5 &
#6).
6.1.1.1 Making a Measurement
■ Turn the rotary switch to the Ω+A position, and wait several seconds
■ Clamp around the conductor to be measured. If the clamp is incorrectly
■ If necessary, use the HOLD button to freeze the measurement.
■ If necessary, use the MEM button to store the measurement.
NOTE: If the measured impedance is less than 1W, the measurement display
alternates between the value measured and the word LOOP, in order to call the
user's attention to the risk of measuring a local loop at the test point that does
not include the earth/ground measurement.
Clamp-on Ground Resistance Tester Model 6417
uality Products Online at:
6. MEASUREMENT MODES
while the instrument performs internal calibration.
closed, the
icon is displayed.