  • Page 1 Clamp-on Ground Tester Model 6417 USER MANUAL ENGLISH GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 2 Statement of Compliance Chauvin Arnoux , Inc. d.b.a. AEMC Instruments ® ® certifies that this instrument has been calibrated using standards and instruments traceable to international standards. We guarantee that at the time of shipping your instrument has met its published specifications.
  • Page 3 5W Calibration Loop Cat. #2141.51 Bluetooth Adapter Cat. #2126.45 Also Included: Quick Start Guide (4) 1.5V AA Batteries (1) Wrist Strap (1) Safety Sheet (20 languages) Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 4 Thank you for purchasing an AEMC Clamp-on Ground Resistance Tester. For best results from your instrument and for your safety, read the enclosed operating instructions carefully and comply with the precautions for use. These products must be only used by qualified and trained users.
  • Page 5 ■ Use extreme caution when using the instrument around energized electrical equipment. ■ Never attempt to use the instrument to twist or pry the ground electrode or ground wire away from the equipment being grounded. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 6: Table Of Contents

    5.2 Setting the Date and Time ..............22 5.3 Display Example .................23 5.4 Turning the Instrument ON ..............23 5.5 Turning Bluetooth ON .................24 5.6 Turning the Instrument OFF..............24 Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at:...
  • Page 7 6.3 Rotary Position - (MR) ................33 6.3.1 Displaying Stored Measurements...........33 7. DATAVIEW SOFTWARE ................36 ® 7.1 Installing DataView ................36 ® 7.2 Ground Clamp Control Panel..............38 8. ANDROID APPLICATION ................39 Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 8 10.1 Cleaning....................47 10.2 Battery Replacement ................47 10.3 Repair and Calibration ..............48 10.4 Technical and Sales Assistance ............48 10.5 Limited Warranty ................49 10.6 Warranty Repairs ................49 Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 9: Introduction

    1.2 Ordering Information Clamp-on Ground Resistance Tester Model 6417 .......Cat. #2141.02 Includes a hard carrying case, Bluetooth USB adapter, calibration loop, four 1.5V AA batteries, quick start guide, and USB stick with DataView software and user ®...
  • Page 10: Product Features

    The Buzzer and Auto Power OFF features can be disabled at any time. The Model 6417 is equipped with an alarm function and a data storage function. In the Alarm mode, the probe will audibly and visually indicate when the reading is beyond an input set point.
  • Page 11: Features

    ■ Designed to EN 61010-1, 600V CAT IV safety standards 2.3 Applications ■ Ground electrode system resistance ■ Bonding/continuity checks ■ Cell tower grounding verification ■ Ground measurements on Railroad signaling systems Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 12: Display

    2.4 Display The Model 6417 is equipped with a 152-segment OLED (organic light-emitting diode) display. This OLED technology results in a thinner, lighter, sharper, higher contrast display compared to LCD displays. Figure 2-1 Item Description Indicates selection of Advanced mode.
  • Page 13 AUTO-HOLD mode. Display of the buzzer’s active state; the icon is not shown when the buzzer is inactive. Selection of the buzzer operating mode is made in SET-UP (see § 4.4, menu #2). Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www.
  • Page 14: Control Features

    OLED Display: Crisp, clean and bright display Rotary Switch: Selects measurement functions and instrument SET-UP HOLD: Freezes last measured value on the display Turns Bluetooth ON/OFF (when switch is set to MR or SET-UP) Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 15: Audible Signals

    Simultaneous selection of the loop impedance measurement and the leakage Ω+A current measurement. Current measurement selection Displays stored measurements. SET-UP Access to the instrument configuration and deletion of stored measurements. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 16: Button Functions

    HOLD button is difficult. If the HOLD button is not pressed during this time, closing the clamp automatically exits the AUTO-HOLD mode. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 17: Principle Of Operation

    In most field applications, the number of electrodes that make up a multi- grounded system would be higher; therefore the equivalent parallel resistance is negligible with respect to the rod under test. Figure 3-1 Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 18 Figure 3-2 Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 19: Set-Up

    Figure 4-1 (menu #5) which displays the voltage alarm threshold adjustment (AL. V). Figure 4-1 Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 20: Selecting A Specific Menu

    StOP ■ Auto Power OFF is deactivated when the icon is visible and activated when it is hidden. ■ Return to the previous menu by ►. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at:...
  • Page 21 Setting the Alarm Value. ■ Press ▲ or ▼ to select the current alarm threshold (Figure 2-1, item #11). ■ Validate and return to the previous menu by ►. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at:...
  • Page 22 ■ Press ▲ or ▼ to select the transposition frequency of the measured impedance from among the four possible values: 50, 60, 128, and 2083 Hz. ■ Validate and return to the previous menu by ►. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 23: Calibration Loop

    4.8Ω and 5.2Ω. If not, clean the instrument and repeat the measurement. If you are still unable to obtain a measurement between 4.8Ω and 5.2Ω, contact AEMC. Figure 4-2 Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www.
  • Page 24: Operation

    NOTE: If time-stamping is not needed, this operation can be skipped by pressing ► button until the measurement screen corresponding to the switch setting Ω +A, A, MR or SET-UP) is displayed. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at:...
  • Page 25: Display Example

    OFF, disconnect it from any conductor and make sure the sensor heads are clean with no obstructions, then turn it back ON. When this adjustment is done, the clamp displays the screen corresponding to the switch setting. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 26: Turning Bluetooth On

    - Contact voltage. - Resistive and inductive components of the loop impedance. The choice of Standard or Advanced mode and the alarm thresholds are configured in SET-UP (see § 4.4, menu #9). Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 27: Memory

    5.8 Memory 5.8.1 Memory Capacity The Model 6417 has a recording capacity of 2000 measurements. The PC interface can be used to activate a circular (first in/first out) recording mode in which the 2000 most recent values are kept, with a maximum sequence number of 9999.
  • Page 28: Using The ▲ And ▼ Buttons

    1: the remaining records may be numbered from 44 to 2043, for example. 5.8.6 Exporting Data to a PC The Model 6417 has a communication capability and can transfer the recorded measurements to a PC using the supplied DataView software (see § 7). 5.9 Alarm Management The device has three distinct alarms that can be configured.
  • Page 29: Current Alarm

    ■ When no alarm is triggered, the alarm threshold is displayed, along with the direction of triggering ( , ) of the impedance, voltage, or current alarm. Figure 5-7 Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 30: Priority Of The Alarms

    ■ The voltage alarm has priority because it concerns the user’s safety. ■ The current alarm is second in priority. ■ The impedance alarm is displayed when no other alarm is triggered. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www.
  • Page 31: Measurement Modes

    Note that the Loop Alarm can be dis- abled via the Control Panel. (See § 7 for information about installing the Ground Clamp Control Panel.) Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www.
  • Page 32: Advanced Mode

    ■ If necessary, use the HOLD button to freeze the measurement. ■ If necessary, use the MEM button to store the measurement. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at:...
  • Page 33: General Information

    This information is displayed in both Standard and Advanced modes. PRODUCT ZxI GREATER THAN 50V - The blinking NOISE symbol is displayed. - The impedance blinks. - The hazardous voltage symbol blinks. Figure 6-5 Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 34 - The impedance is replaced by - - - - Figure 6-8 CURRENT GREATER THAN 40A If the current is greater than 40A: - The current display indicates O.R (Over Range). Figure 6-9 Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 35: Rotary Position (A)

    ■ Set the function switch to the MR position. ■ The type of data that is displayed is dependent on whether Standard or Advanced mode was selected during SET-UP (see § 4.4, menu #9). Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www.
  • Page 36 - Figure 6-14 illustrates an impedance Figure 6-14 and current measurement. - Press ► to display the next screen. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 37 - Press ► to return to the first screen. - To exit from the MR mode, set the rotary switch to the desired mode. Figure 6-17 Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at:...
  • Page 38: Dataview ® Software

    DataView is a software program that enables a computer to connect to and interact with a variety of AEMC instruments, including the Model 6417. As its name implies, a primary purpose of DataView is to view data that has been recorded by the instrument and displayed on the computer.
  • Page 39 3 is highlighted.) You are now prompted to select the software you want to install. Each AEMC product family has its own specially designed Control Panel. If you are performing a Complete install, by default all available Control Panels are selected (a check mark next to the Control Panel indicates it is selected).
  • Page 40: Ground Clamp Control Panel

    You can access all DataView features through either the DataView icon or the Control Panel icon. For users who interact with Model 6417, we recommend primarily using the Control Panel. However, there are situations where using the core DataView icon may be more convenient for some users, such as when viewing multiple archived reports from different AEMC product families.
  • Page 41: Android Application

    Android device. The Ground Tester 6417 app, distributed through the Google Play Store, provides a quick, convenient, and mobile option for working with a Model 6417. Through a simple, easy-to-learn interface, the app provides a substantial subset of the features and functionality offered in AEMC’s DataView data analysis software, without requiring a PC.
  • Page 42 The Ground Tester 6417 app enables users to connect to the Model 6417 via Bluetooth. Once connected, you can view data currently being measured by the instrument in real-time. Real-time measurements can be displayed as both numerical data and as graphical trends.
  • Page 43 These records can later be viewed on the device. They can also be emailed to others for further distribution and analysis. In addition, records can be used to generate reports in text, Excel-compatible, or .icp (DataView) format. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www.
  • Page 44 You can also use the app to modify a variety of configuration settings on the Model 6417. Figure 8-4 The Ground Tester 6417 app can be downloaded free from the Google Play Store (see ) and is available in multiple languages.
  • Page 45: Specifications

    ±5% ±5W 400 to 590W ±10% ±10W 600 to 1150W 20% approx 1200 to 1500W 25% approx Alarm: range of threshold from 1 to 199W. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 46: Loop Inductance Measurement

    100.0 to 299.0mA ±2% ±1mA 0.300 to 0.990A 1.000 to 2.990A 10mA ±2% ±10mA 3.00 to 39.99A Alarm: Range of thresholds from 1mA to 40A. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 47: Power Supply

    Dimensions: 2.16 x 3.74 x 10.31" (55 x 95 x 262mm) Weight: 2.06 lbs (935g) approx. with batteries Environmental: IP40, group III equipment Drop Test: According to IEC-61010-1 Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at:...
  • Page 48: Safety

    Pollution degree: 2 Overvoltage category: 600V CAT IV ■ Emissions and immunity in an industrial setting compliant with IEC 61326-1 Specifications are subject to change without notice. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at:...
  • Page 49: Maintenance

    IEC ■ Never use alcohol, solvents or hydrocarbons. 10.2 Battery Replacement The Model 6417 is powered by four 1.5V batteries. The battery replacement indicator will blink when battery voltage is low and will display continuously when battery replacement is required.
  • Page 50: Repair And Calibration

    If you are experiencing any technical problems, or require any assistance with the proper operation or application of your instrument, please call, mail, fax or e-mail our technical support team: NOTE: Do not ship Instruments to our Foxborough, MA address. Clamp-on Ground Resistance Tester Model 6417 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...
  • Page 51: Limited Warranty

    10.5 Limited Warranty The Clamp-on Ground Tester Model 6417 is warranted to the owner for a period of two years from the date of original purchase against defects in manufacture. This limited warranty is given by AEMC Instruments, not by the distributor from ®...
  • Page 52 10/19 99-MAN 100395 v11 GlobalTestSupply www. .com Find Quality Products Online at: sales@GlobalTestSupply.com...