Loop Inductance Measurement; Contact Voltage (Touch Voltage); Current Measurement - AEMC 6417 User Manual

Clamp-on ground resistance tester
Hide thumbs Also See for 6417:
Table of Contents

Advertisement

Measurement Frequency: 2083Hz
Frequency Selection: Choice of 50, 60, 128, or 2083Hz for the impedance
calculation
Maximum overloads: - permanent current 100A maximum (50/60Hz)

9.2.2 Loop Inductance Measurement

Measurement Range
10 to 100µH
100 to 500µH

9.2.3 Contact Voltage (Touch Voltage)

Contact Voltage Function: Value calculated as the product of the loop
impedance by the leakage current.
Measurement Range
5.0 to 49.5V
50.0 to 75.0V
Alarm: Range of thresholds from 1V to 75V.

9.2.4 Current Measurement

Ammeter Function: 0.2 to 40A. 4000-count display.
Measurement Range
0.200 to 0.999mA
1.000 to 2.990mA
3.00 to 9.99mA
10.00 to 29.90mA
30.0 to 99.9mA
100.0 to 299.0mA
0.300 to 0.990A
1.000 to 2.990A
3.00 to 39.99A
Alarm: Range of thresholds from 1mA to 40A.
Clamp-on Ground Resistance Tester Model 6417
uality Products Online at:
- transient current (<5s) 200A (50/60Hz)
0.1 to 4.9V
GlobalTestSupply
www.
Resolution
1µH
1µH
Resolution
0.1V
0.5V
1V
Resolution
1µA
10µA
100µA
1mA
10mA
Accuracy
±5% ±1µH
±3% ±1µH
Accuracy
±5% ±0.1V
±5% ±0.5V
±10% ±1V
Accuracy
±2% ±50µA
±2% ±50µA
±2% ±100µA
±2% ±1mA
±2% ±10mA
.com
sales@GlobalTestSupp
51