GE Multilin F35 Instruction Manual page 420

Multiple feeder protection system ur series
Table of Contents

Advertisement

B.4 MEMORY MAPPING
F502
BITFIELD: ELEMENT OPERATE STATES
Each bit contains the operate state for an element. See the F124
format code for a list of element IDs. The operate bit for element ID
X is bit [X mod 16] in register [X/16].
B
F504
BITFIELD: 3-PHASE ELEMENT STATE
bitmask
element state
0
Pickup
1
Operate
2
Pickup Phase A
3
Pickup Phase B
4
Pickup Phase C
5
Operate Phase A
6
Operate Phase B
7
Operate Phase C
F505
BITFIELD: CONTACT OUTPUT STATE
0 = Contact State, 1 = Voltage Detected, 2 = Current Detected
F507
BITFIELD: COUNTER ELEMENT STATE
0 = Count Greater Than, 1 = Count Equal To, 2 = Count Less Than
F509
BITFIELD: SIMPLE ELEMENT STATE
0 = Operate
F511
BITFIELD: 3-PHASE SIMPLE ELEMENT STATE
0 = Operate, 1 = Operate A, 2 = Operate B, 3 = Operate C
F512
ENUMERATION: HARMONIC NUMBER
bitmask
harmonic
0
2ND
1
3RD
2
4TH
3
5TH
4
6TH
5
7TH
6
8TH
7
9TH
8
10TH
9
11TH
10
12TH
11
13TH
B-70
bitmask
harmonic
12
14TH
13
15TH
14
16TH
15
17TH
16
18TH
17
19TH
18
20TH
19
21ST
20
22ND
21
23RD
22
24TH
23
25TH
F35 Multiple Feeder Protection System
F515
ENUMERATION ELEMENT INPUT MODE
0 = Signed, 1 = Absolute
F516
ENUMERATION ELEMENT COMPARE MODE
0 = Level, 1 = Delta
F518
ENUMERATION: FLEXELEMENT™ UNITS
0 = Milliseconds, 1 = Seconds, 2 = Minutes
F519
ENUMERATION: NON-VOLATILE LATCH
0 = Reset-Dominant, 1 = Set-Dominant
F522
ENUMERATION: TRANSDUCER DCMA OUTPUT RANGE
0 = –1 to 1 mA; 1 = 0 to 1 mA; 2 = 4 to 20 mA
F523
ENUMERATION: DNP OBJECTS 20, 22, AND 23 DEFAULT
VARIATION
bitmask
default variation
0
1
1
2
2
5
3
6
F524
ENUMERATION: DNP OBJECT 21 DEFAULT VARIATION
bitmask
Default Variation
0
1
1
2
2
9
3
10
F525
ENUMERATION: DNP OBJECT 32 DEFAULT VARIATION
bitmask
default variation
0
1
1
2
2
3
3
4
4
5
5
7
APPENDIX B
GE Multilin

Advertisement

Table of Contents
loading