GE Multilin F35 Instruction Manual page 388

Multiple feeder protection system ur series
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 31 of 48)
ADDR
REGISTER NAME
Digital Counter (Read/Write Setting) (8 modules)
A800
Digital Counter 1 Function
A801
Digital Counter 1 Name
A807
Digital Counter 1 Units
A80A
Digital Counter 1 Block
B
A80B
Digital Counter 1 Up
A80C
Digital Counter 1 Down
A80D
Digital Counter 1 Preset
A80F
Digital Counter 1 Compare
A811
Digital Counter 1 Reset
A812
Digital Counter 1 Freeze/Reset
A813
Digital Counter 1 Freeze/Count
A814
Digital Counter 1 Set To Preset
A815
Reserved (11 items)
A820
...Repeated for Digital Counter 2
A840
...Repeated for Digital Counter 3
A860
...Repeated for Digital Counter 4
A880
...Repeated for Digital Counter 5
A8A0
...Repeated for Digital Counter 6
A8C0
...Repeated for Digital Counter 7
A8E0
...Repeated for Digital Counter 8
IEC 61850 received analog settings (read/write)
AA00
IEC 61850 GOOSE analog 1 default value
AA02
IEC 61850 GOOSE analog input 1 mode
AA03
IEC 61850 GOOSE analog input 1 units
AA05
IEC 61850 GOOSE analog input 1 per-unit base
AA07
...Repeated for IEC 61850 GOOSE analog input 2
AA0E
...Repeated for IEC 61850 GOOSE analog input 3
AA15
...Repeated for IEC 61850 GOOSE analog input 4
AA1C
...Repeated for IEC 61850 GOOSE analog input 5
AA23
...Repeated for IEC 61850 GOOSE analog input 6
AA2A
...Repeated for IEC 61850 GOOSE analog input 7
AA31
...Repeated for IEC 61850 GOOSE analog input 8
AA38
...Repeated for IEC 61850 GOOSE analog input 9
AA3F
...Repeated for IEC 61850 GOOSE analog input 10
AA46
...Repeated for IEC 61850 GOOSE analog input 11
AA4D
...Repeated for IEC 61850 GOOSE analog input 12
AA54
...Repeated for IEC 61850 GOOSE analog input 13
AA5B
...Repeated for IEC 61850 GOOSE analog input 14
AA62
...Repeated for IEC 61850 GOOSE analog input 15
AA69
...Repeated for IEC 61850 GOOSE analog input 16
IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting)
AA80
Default GOOSE/GSSE Update Time
AA81
IEC 61850 GSSE Function (GsEna)
AA82
IEC 61850 GSSE ID
AAA3
IEC 61850 GOOSE Function (GoEna)
AAA4
IEC 61850 GSSE Destination MAC Address
AAA7
IEC 61850 Standard GOOSE ID
AAC8
IEC 61850 Standard GOOSE Destination MAC Address
AACB
IEC 61850 GOOSE VLAN Transmit Priority
AACC
IEC 61850 GOOSE VLAN ID
AACD
IEC 61850 GOOSE ETYPE APPID
AACE
Reserved (2 items)
B-38
RANGE
0 to 1
---
---
0 to 65535
0 to 65535
0 to 65535
–2147483647 to
2147483647
–2147483647 to
2147483647
0 to 65535
0 to 65535
0 to 65535
0 to 65535
---
–1000000 to 1000000
0 to 1
---
0 to 999999999.999
1 to 60
0 to 1
---
0 to 1
---
---
---
0 to 7
0 to 4095
0 to 16383
0 to 1
F35 Multiple Feeder Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F102
---
---
F205
---
---
F206
---
1
F300
---
1
F300
---
1
F300
---
1
F004
---
1
F004
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
---
F001
---
0.001
F060
---
1
F491
0 (Default Value)
---
---
F207
---
0.001
F060
s
1
F001
---
1
F102
---
---
F209
---
1
F102
---
---
F072
---
---
F209
---
---
F072
---
1
F001
---
1
F001
---
1
F001
---
1
F001
DEFAULT
0 (Disabled)
"Counter 1"
(none)
0
0
0
0
0
0
0
0
0
0
1000
(none)
1
60
1 (Enabled)
"GSSEOut"
0 (Disabled)
0
"GOOSEOut"
0
4
0
0
0
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents