5 SETTINGS
PATH: SETTINGS
PRODUCT SETUP
ACCESS LEVEL
TIMEOUTS
MESSAGE
These settings allow the user to specify the length of inactivity required before returning to the restricted access level. Note
that the access level will set as restricted if control power is cycled.
COMMAND LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
SETTING LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
PATH: SETTINGS
PRODUCT SETUP
DISPLAY
PROPERTIES
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
LANGUAGE: This setting selects the language used to display settings, actual values, and targets. The range is
dependent on the order code of the relay.
FLASH MESSAGE TIME: Flash messages are status, warning, error, or information messages displayed for several
seconds in response to certain key presses during setting programming. These messages override any normal mes-
sages. The duration of a flash message on the display can be changed to accommodate different reading rates.
DEFAULT MESSAGE TIMEOUT: If the keypad is inactive for a period of time, the relay automatically reverts to a
default message. The inactivity time is modified via this setting to ensure messages remain on the screen long enough
during programming or reading of actual values.
DEFAULT MESSAGE INTENSITY: To extend phosphor life in the vacuum fluorescent display, the brightness can be
attenuated during default message display. During keypad interrogation, the display always operates at full brightness.
SCREEN SAVER FEATURE and SCREEN SAVER WAIT TIME: These settings are only visible if the F35 has a liquid
crystal display (LCD) and control its backlighting. When the
is turned off after the
DEFAULT MESSAGE TIMEOUT
have been pressed and no target messages are active. When a keypress occurs or a target becomes active, the LCD
backlighting is turned on.
GE Multilin
SECURITY
ACCESS SUPERVISION
COMMAND LEVEL ACCESS
TIMEOUT: 5 min
SETTING LEVEL ACCESS
TIMEOUT: 30 min

DISPLAY PROPERTIES

LANGUAGE:
English
FLASH MESSAGE
TIME:
1.0 s
DEFAULT MESSAGE
TIMEOUT: 300 s
DEFAULT MESSAGE
INTENSITY: 25 %
SCREEN SAVER
FEATURE: Disabled
SCREEN SAVER WAIT
TIME: 30 min
CURRENT CUT-OFF
LEVEL: 0.020 pu
VOLTAGE CUT-OFF
LEVEL: 1.0 V
SCREEN SAVER FEATURE
followed by the
F35 Multiple Feeder Protection System
5.2 PRODUCT SETUP
ACCESS LEVEL TIMEOUTS
Range: 5 to 480 minutes in steps of 1
Range: 5 to 480 minutes in steps of 1
5.2.2 DISPLAY PROPERTIES
Range: English; English, French; English, Russian;
English, Chinese
(range dependent on order code)
Range: 0.5 to 10.0 s in steps of 0.1
Range: 10 to 900 s in steps of 1
Range: 25%, 50%, 75%, 100%
Visible only if a VFD is installed
Range: Disabled, Enabled
Visible only if an LCD is installed
Range: 1 to 65535 min. in steps of 1
Visible only if an LCD is installed
Range: 0.002 to 0.020 pu in steps of 0.001
Range: 0.1 to 1.0 V secondary in steps of 0.1
is "Enabled", the LCD backlighting
, providing that no keys
SCREEN SAVER WAIT TIME
5
5-11