5 SETTINGS
The GGIO1 status configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
GGIO1 STATUS
CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
The
NUMBER OF STATUS POINTS IN GGIO1
instantiated in the GGIO1 logical node. Changes to the
the F35 is restarted.
The GGIO2 control configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
GGIO2 CF SPCSO 1
The GGIO2 control configuration settings are used to set the control model for each input. The available choices are "0"
(status only), "1" (direct control), and "2" (SBO with normal security). The GGIO2 control points are used to control the F35
virtual inputs.
The GGIO4 analog configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
GGIO4 ANALOG
CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
The
NUMBER OF ANALOG POINTS
changed, the F35 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newly
configured number of analog points.
GE Multilin
COMMUNICATIONS
IEC 61850...
NUMBER OF STATUS
POINTS IN GGIO1: 8
GGIO1 INDICATION
Off
GGIO1 INDICATION
Off
GGIO1 INDICATION 128
Off
setting specifies the number of "Ind" (single point status indications) that are
NUMBER OF STATUS POINTS IN GGIO1
COMMUNICATIONS
IEC 61850...
GGIO2 CF SPCSO 1
CTLMODEL: 1
COMMUNICATIONS
IEC 61850...
NUMBER OF ANALOG
POINTS IN GGIO4:
GGIO4 ANALOG
MEASURED VALUE
GGIO4 ANALOG
MEASURED VALUE
GGIO4 ANALOG 32
MEASURED VALUE
setting determines how many analog data points will exist in GGIO4. When this value is
F35 Multiple Feeder Protection System
GGIO1 STATUS CONFIGURATION
Range: 8 to 128 in steps of 8
Range: FlexLogic™ operand
1
Range: FlexLogic™ operand
2
Range: FlexLogic™ operand
setting will not take effect until
GGIO2 CONTROL...
Range: 0, 1, or 2
GGIO4 ANALOG CONFIGURATION
Range: 4 to 32 in steps of 4
8
1
2
5.2 PRODUCT SETUP
GGIO2 CF SPSCO 1(64)