6 ACTUAL VALUES
CHANNEL 1 STATUS: This represents the receiver status of each channel. If the value is "OK", teleprotection is
enabled and data is being received from the remote terminal; If the value is "FAIL", teleprotection enabled and data is
not being received from the remote terminal. If "n/a", teleprotection is disabled.
CHANNEL 1 LOST PACKETS: Data is transmitted to the remote terminals in data packets at a rate of two packets per
cycle. The number of lost packets represents data packets lost in transmission; this count can be reset to 0 through the
COMMANDS
CLEAR RECORDS
VALIDITY OF CHANNEL CONFIGURATION: This value displays the current state of the communications channel
identification check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the
"FAIL" message will be displayed. The "N/A" value appears if the local relay ID is set to a default value of "0", the chan-
nel is failed, or if the teleprotection inputs/outputs are not enabled.
PATH: ACTUAL VALUES
STATUS
INCIPIENT FAULT 1
MESSAGE
MESSAGE
The number of detected incipient faults for each incipient fault element are displayed here for each phase. These values
can be reset to zero with the
COMMANDS
PATH: ACTUAL VALUES
STATUS

ETHERNET SWITCH

MESSAGE
MESSAGE
MESSAGE
These actual values appear only if the F35 is ordered with an Ethernet switch module (type 2S or 2T). The status informa-
tion for the Ethernet switch is shown in this menu.
SWITCH 1 PORT STATUS to SWITCH 6 PORT STATUS: These values represents the receiver status of each port on
the Ethernet switch. If the value is "OK", then data is being received from the remote terminal; If the value is "FAIL",
then data is not being received from the remote terminal or the port is not connected.
SWITCH MAC ADDRESS: This value displays the MAC address assigned to the Ethernet switch module.
GE Multilin
menu.
INCIPIENT FAULT
INCIPIENT FAULT 1(6)
INCIPIENT FAULT 1
PH A FAULTS: 0
INCIPIENT FAULT 1
PH B FAULTS: 0
INCIPIENT FAULT 1
PH C FAULTS: 0
CLEAR RECORDS
ETHERNET SWITCH
SWITCH 1 PORT
STATUS: OK
SWITCH 2 PORT
STATUS: OK
SWITCH 6 PORT
STATUS: OK
SWITCH MAC ADDRESS:
00A0F40138FA
F35 Multiple Feeder Protection System

6.2.17 INCIPIENT FAULT DETECTOR

Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
CLEAR INCIPENT FAULT COUNTERS
6.2.18 ETHERNET SWITCH
Range: FAIL, OK
Range: FAIL, OK
Range: FAIL, OK
Range: standard MAC address format
6.2 STATUS